To start, select the product of your interest in the left column. Then take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas will first be moderated before they are made visible to other users of this portal.

This page is for feedback for specific AVEVA solutions, excluding PI Systems and Data Hub. For links to these other feedback portals, please see the tab RESOURCES below.

Status Implemented
Portfolio area Plant SCADA
Products Other
Created by Guest
Created on Jan 19, 2023

Disable the extra Citect32 executables if the new web component is not used

In V2023 a new chromium web component was introduced. This causes extra Citect32 processes started. The ExampleSA project starts 10 Citect32.exes instead of the 5 (I/Om Alarm, Trend, Report and Client) you would expect (not in service mode). Would be nice to disable it using a parameter or not starting these extra Citect32's if the web component isn't used on any pages of the project (even better)

Idea business value

There are SI's and end-users who have tooling for monitoring the number of instances of the Citect32.exe.

Idea priority 4 – Important to my company
  • Attach files
  • Admin
    Nathan Slider
    Reply
    |
    Jul 17, 2023

    Thanks for the feedback and feature improvement idea. This has been enhanced in the latest Plant SCADA 2023 July update 7. Runtime

    2295143 - INI parameter required to disable Web Content

    A new INI parameter [Animator]EnableWebContent has been added. Set this to 0 (default = 1) to disable Web Content at runtime. This will prevent the creation of extra Citect32 processes.

  • +9