To start, select the product of your interest in the left column. Then take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas will first be moderated before they are made visible to other users of this portal.

This page is for feedback for specific AVEVA solutions, excluding PI Systems and Data Hub. For links to these other feedback portals, please see the tab RESOURCES below.

Status Waiting for information
Portfolio area Enterprise SCADA Server
Products Replication
Created by Guest
Created on Nov 23, 2023

Analog field rawval should be replicated to non-owning sites

Client has observed that the ANALOG "rawval" field is not replicating to non-owning sites; and they expect this value to be replicated.


Anything else relevant to this feature?
There is an optional feature called the "Raw Data Enhancement" RAW_ENABLED and RAW_REPLICATION, which is turned off by default due to the impact on replication. Suggested that this be considered also for bringing into the FUNC rep. Would also need to ensure that this is versioned for upgradability. This was probably designed for a gas system which has significantly less IO than a liquids system.

Expectation

Are the other options?

The hybrid DSS does not solve this issue.


Why not simply edit the replication subscription?

Data replication will be triggered every single time, and it is more data to replicate than the functional replication that sends fewer fields.

This consumes lots of bandwidth to be consumed, and was determined to be a non-starter - it has been tried at other customers - they saw table locking and integrity update storms. For gas customers it might work. For liquids it likely wont. A PSR test would help to confirm. There have been many enhancements to replication since 2018/7.6 when this was last tried.

Idea business value

Operational Impact

During Point-Point testing, client has operators login to DSS system (non-owning). They use the rawval to confirm "Raw to ENGR" and "scaling".

How critical is this? how often do they need it?

Customer was upset when they found it. They didn't find it right away, but they may have changed their processes that increased the use of the DSS for this.

Customers are sensitive when they find what they feel might be a bug in replication. It is important to stress that this was a design decision at the time, and one which apparently hasn't stood up to the test of time as the use of the DSS continues to evolve.

Idea Type Improvement
Idea priority 4 – Important to my company
User Persona Field Technician
Work in
OASYS-785 Raw value replication to non owning sites
Work status
  • Attach files
  • Admin
    Jake Hawkes
    Reply
    |
    Aug 9, 2024

    Is the request to add the rawval field to the funcrep subscription, so that it is sent to the non-owning in the least bandwidth-consuming way? Adding the single field to the subscription is not desired? Or is only needed temporarily?